. End of Season Maintenance.
Turn off the water supply.
Remove filter pad frames.
Turn off the power at the isolating switch inside cabinet, or on the corner pillar.
Hose both sides of the filter pad frames to remove dust, salts, pollen etc.
Warning! Do not use high water pressure when cleaning Chillcel
®
pads- Damage will occur.
Check and clean the water distributor channels.
Empty the water reservoir through the outlet provided.
Thoroughly clean the reservoir.
Do not replace the drain outlet. If fitted with a drain valve, ensure that it is open.
Ensure that there is no evidence that water is carrying over onto the motor or pumps. If so,
check the pad condition.
Check the fan blades are tight.
Check Pulleys and Belts for wear.
Check alignment and tensioning.
Replace or adjust parts if necessary.
Leave Isolating switch OFF and refit pad frames.
REGULAR MAINTENANCE IS ESSENTIAL FOR MAXIMUM EFFICIENCY
To ensure that your Braemar Evaporative Air conditioner remains in first class working
condition for many years, it should be thoroughly serviced four (4) times a year. Service
schedules should include a service at the end of the summer season and prior to the
commencement of the next summer season.
Service & Maintenance
11. Lubrication - All models.
Bearings on electric motors and water pumps are sealed for life and do not require
lubrication. The same applies to the fan shaft bearings on the RPB600-RPB1000.
RPB1200 - RPB1800 fan shafts are fitted with plumber blocks with grease nipples, lubricate
at regular intervals, depending on frequency of use.
. Health Regulations.
Please note that some State Regulations require that Evaporative Air Conditioners
used for Commercial purposes must be serviced at Three ( 3 ) Monthly Intervals.
Owners of Commercial Air Conditioners should contact the Health Authority in their State for
servicing guidelines.